Permit Number: T13CM03512
Parcel: 11942006J

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03512
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2013 DAVID RIVERA ZONING REVIEW Approved
06/10/2013 LOREN MAKUS ENGINEERING REVIEW Approved
06/11/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/11/2013 CARL SCHULTZ FIRE REVIEW Approved
06/11/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
06/12/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
06/12/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/12/2013 ROBERT SHERRY WATER REVIEW Approved
06/12/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/18/2013 CPIERCE1 WWM REVIEW Needs Review