Permit Number: T13CM03474
Parcel: 113043470

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T13CM03474
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2013 MARTIN BROWN FIRE REVIEW Approved
08/01/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/01/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/01/2013 DAVID RIVERA ZONING REVIEW Approved
08/01/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/01/2013 ROBERT SHERRY WATER REVIEW Approved
08/01/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. HP-2 is scheduled with an EER of 10.5, Table C403.2.3 (2) indicates a minimum EER of 11.0 for this unit capacity.
2. Show that the proposed HVAC systems meet the control requirements of Sections C403.2.4 and C403.3. Reference: Section C303.1, International Energy Conservation Code 2012.
08/01/2013 LOREN MAKUS ENGINEERING REVIEW Approved
08/01/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/02/2013 SHANAE POWELL OUT TO CUSTOMER Completed