| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/13/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The plans indicate that conditioned air is now being supplied to the restrooms but the electrical plans indicate that the exhaust fans are now to be controlled with occupancy sensors. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated. Reference: Section 403.2.1 (4), IMC 2012. 2. Detail 5/M2.0 shows grease duct enclosure material (fire wrap blanket) being used to provide clearance to combustibles where the hood penetrates the ceiling. This practice has been specifically prohibited by Section 507.10, IMC 2012 because the grease duct enclosure material has not been listed for this use. See Section 506.3.11, IMC 2012 for the enclosure requirements. 3. Verify the ventilation calculations have used an Ez (zone air distribution effectiveness) factor of 1 per footnote g, Table 403.3.1.2, IMC 2012. Reference: Section C403.2.5, IECC 2012. |
| 06/13/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/19/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 06/19/2013 | CPIERCE1 | REJECT SHELF | Completed |