Permit Number: T13CM03442
Parcel: 12709007J

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03442
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2013 TERRY STEVENS ZONING REVIEW Approved
06/06/2013 LOREN MAKUS ENGINEERING REVIEW Approved
06/06/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/06/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/19/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The city of Tucson has adopted the 2012 IMC, not the 2007 edition of ASHRAE 62.1. Revise the calculations, using a zone air distribution effectivness factor of 0.8 (ceiling supply/ceiling return with supply air temperature greater than 15 degrees Fahrenheit above the room temperature).
06/19/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/19/2013 ROBERT SHERRY WATER REVIEW Approved
06/19/2013 MARTIN BROWN FIRE REVIEW Approved
06/19/2013 CHAD AMATEAU WWM REVIEW Approved
06/19/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed