Permit Number: T13CM03401
Parcel: 116205360

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T13CM03401
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2013 MICHAEL ST. PAUL ZONING REVIEW Denied Stamped approval must be on all of the sheet from the Mercado District.
06/24/2013 FERNE RODRIGUEZ LANDFILL ENVIRONMENTAL SERVICES Approved APPROVED BY JEFFREY DRUMM
06/27/2013 ANDREW CONNOR NPPO REVIEW Approved
07/15/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T13CM03401
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FOUNDATION PLANS:

1. Show compliance with termite treatment, R320.
2. Revise the Foundation Plan for accommodating all load bearing walls, R401.2. Include interior bearing walls on sheet S2.0. The wall line between Garage and Stairway requires Braced Wall panel connections, R602.10.8.
3. Notate the grade away from foundations with a minimum 6" fall within the first 10', R401.3.

MECHANICAL PLANS:

1. The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Update the reference at Note #7.

ELECTRICAL PLANS:

1. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
2. Protect all 15A & 20A proposed outlets (except bathrooms and kitchen) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/18/2013 CPIERCE1 REJECT SHELF Completed