Permit Number: T13CM03400
Parcel: 116205720

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM

Permit Number - T13CM03400
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2013 MICHAEL ST. PAUL ZONING REVIEW Denied The Mercado District approval stamp must be on all sheets of the plan.

The easements must be delineated and dimensioned, with the purose of the easements stated on the plot plan for each lot. The easement must be recorded for each lot and the recording documentation must be provided and referenced on each plot plan.
07/19/2013 LOREN MAKUS ENGINEERING REVIEW Denied July 10, 2013

Provide dimension of the adjacent right of way including sidewalk and curb locations. Provide dimensions from the curb access ramp to the proposed driveway. There must be a minimum of 4 feet between the ends of the curb transitions for the adjacent aprons.
07/19/2013 ANDREW CONNOR NPPO REVIEW Denied Mitigation for removal of Native Mequite within ROW required .
07/23/2013 KEN BROUILLETTE FIRE REVIEW Approved
07/23/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 7-25-13
Activity: T13CM03400
Address: 902 W. Calle de los Higos
Applicant: Innovative Living Design & Development

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

PLUMBING PLAN:
1. Pressure and temperature relief valve for the water heater may terminate no more than 6 inches above the grade, P2803.6.1. Note on plan say 6' above grade.
2. The kitchen sink, laundry sink, and garage sink are not considered gray water fixtures. Adjust the waste layout accordingly.
3. Provide both gray water AND black water discharges from the clothes washing machine.
4. The Tucson Water policy adopted 7/13/12 limits the maximum demand for water meters. Specify the size of the proposed water meter.
5. Specify the maximum developed length of water line from the meter the furthest appliance served, and the lowest available working pressure after pressure loss calculation for elevation, P2903.7.
6. Isometric drawings of DWV systems are required for multiple story buildings.
7. Provide a gas line isometric and size the supply pipe for the connected demand. Include the length of line and BTU demand for each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system, G2413.1, Table G2413.4 (1).

MECHANICAL PLAN:
8. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.

ELECTRICAL PLAN:
9. Specify faceplate grounding per E4001.11.1.
10. Specify tamper resistant receptacles per E4002.14.
11. Exterior outlets at grade level shall be provided at both the front and back of the dwelling, E3901.7. These outlets shall be GFCI protected E3902.3.
12. Provide floor receptacles at spaces in exterior walls occupied by fixed panels of glass so that no point is more than 6 feet from an outlet, E3901.2.1, E3901.2.2(2).

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2013 CPIERCE1 REJECT SHELF Completed