Permit Number: T13CM03301
Parcel: 12317252B

Address:
1510 N VINE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03301
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2013 STEVE SHIELDS ZONING REVIEW Approved
05/31/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/31/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the installation of the flow control device so that no plumbing vent is located between the air vent of the flow control device and the hydromechanical grease interceptor. Reference: Section 303.2, IPC 2012.
(see also: http://www.pdionline.org/storage/publications/Guide-To-Grease-Interceptors.pdf)
05/31/2013 ROBERT SHERRY WATER REVIEW Approved
05/31/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/31/2013 LOREN MAKUS ENGINEERING REVIEW Approved
05/31/2013 MARTIN BROWN FIRE REVIEW Approved
05/31/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/03/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
06/13/2013 CPIERCE1 WWM REVIEW Needs Review