Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM03181
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/30/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Correct the calculated sensible load for AC-1 to correspond to the results of the load calculation program (Carrier HAP or Carrier Block Load). 2. Verify that 10-32 threaded rod is adequate to support the ceiling-mounted fans considering the distance from the roof structure to the ceiling. 3. Show that the proposed HVAC system meets the requirements of Sections C403.2, C403.3 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012. |
| 05/31/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Verify that the modifications to the hot water distribution system will result in the distance from the hot water source (e.g. recirculated hot water piping) to the fixtures that require hot water is not greater than 50 feet. Reference: Section 607.2, IPC 2012. 2. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches (e.g. the new 4" horizontal drain requires a cleanout). Reference: Section 708.7, IPC 2012. 3. Based on the pipe lengths shown on detail 5/P0.2, the developed length of the natural gas pipe from the meter to AC-1 is 76 feet, not 64 feet. Using the 80-foot column in Table 402.4 (2), IFGC 2012, the section of pipe serving AC-1 should be ¾", not ½". |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/10/2013 | CPIERCE1 | REJECT SHELF | Completed |