Permit Number: T13CM03181
Parcel: 11207461C

Address:
2901 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03181
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-2; FLOOR PLAN: PER THE IBC SECTION 1014.2(4), EXIT EGRESS SHALL NOT PASS THROUGH STORAGE ROOMS. REVISE.
2. SHEET A-2; FLOOR PLAN: PER THE IBC TABLE 1018.1, THE CORRIDOR WALLS MUST HAVE A FIRE RESISTANCE RATING OF ONE HOUR. REVISE THOSE WALLS.
3. SHEET A-3; DETAIL 1: PROVIDE THE BRACING SIZE AND INDICATE THE CONNECTION QUANTITY AND SIZE TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/24/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
05/24/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM03181

1. Mechanical requirement to have exhaust fan energized when conditioned air supplied to room.See Mech Plns Examiner review comments.
2. Why does rear exit not require an exit sign ?

Ray T Majuta
Elect Pln Review
PDSD, Tucson
5/24/2013
Ray.Majuta@tucsonaz.gov
05/24/2013 ROBERT SHERRY WATER REVIEW Approved
05/24/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/24/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
05/28/2013 CPIERCE1 WWM REVIEW Needs Review
05/28/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
05/28/2013 JASON GREEN ENGINEERING REVIEW Approved
05/28/2013 KEN BROUILLETTE FIRE REVIEW Approved