Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM03181
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/24/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-2; FLOOR PLAN: PER THE IBC SECTION 1014.2(4), EXIT EGRESS SHALL NOT PASS THROUGH STORAGE ROOMS. REVISE. 2. SHEET A-2; FLOOR PLAN: PER THE IBC TABLE 1018.1, THE CORRIDOR WALLS MUST HAVE A FIRE RESISTANCE RATING OF ONE HOUR. REVISE THOSE WALLS. 3. SHEET A-3; DETAIL 1: PROVIDE THE BRACING SIZE AND INDICATE THE CONNECTION QUANTITY AND SIZE TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
05/24/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
05/24/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM03181 1. Mechanical requirement to have exhaust fan energized when conditioned air supplied to room.See Mech Plns Examiner review comments. 2. Why does rear exit not require an exit sign ? Ray T Majuta Elect Pln Review PDSD, Tucson 5/24/2013 Ray.Majuta@tucsonaz.gov |
05/24/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/24/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/24/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
05/28/2013 | CPIERCE1 | WWM | REVIEW | Needs Review | |
05/28/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
05/28/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
05/28/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved |