Permit Number: T13CM03120
Parcel: 12105004A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03120
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Verify the supply air flow rate for AC-2; it is shown as 1400 CFM on sheet M1.1 but is scheduled for 1450 CFM. [Initial Comment: Coordinate the supply air flow rates shown on sheet M1.1 for AC-2, AC-4, and AC-6 with the scheduled supply air flow rates.]
2. Revisit the outside air calculations shown on sheet M9.1: the uncorrected outside air flow rate is to include the product of the room area and the required CFM per square feet of room area. [Initial Comment: Correct the ventilation calculations for AC-3, AC-4, AC-5, and AC-6; the total outside air requirement needs to include the CFM per square foot component. Reference: Section 403.3, IMC 2012.]
3. Clarify how the automatic start capability, described in Section C403.2.4.3.3, IECC 2012, has been incorporated in note C of detail 2/M7.1. [Initial Comment: Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown, automatic start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.]
07/10/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/11/2013 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 2222 N. Craycroft
T13CM03120
Structural Plan (2nd Review)

TRANSMITTAL DATE: July 11, 2013

1. The structural plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the structural plans until the development package has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
07/12/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A4.1; RESTROOM ELEVATIONS 3 AND 4: THE LOCATION OF THE HORIZONTAL GRAB BAR ABOVE THE FLOOR SHOULD BE REVISED PER ICC/ANSI FIGURE 609.4.2 FOR CHILDREN.
2. SHEET A4.1; RESTROOM ELEVATIONS 3 AND 4: THE LOCATION OF THE VERTICAL GRAB BAR ABOVE THE FLOOR AND FROM THE WALL SHOULD BE REVISED PER ICC/ANSI FIGURE 609.4.2 FOR CHILDREN.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2013 SHANAE POWELL OUT TO CUSTOMER Completed
08/09/2013 CPIERCE1 REJECT SHELF Completed