Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM03102
Parcel: 13507461C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03102
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
05/22/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the proposed HVAC system and equipment meets the requirements of Sections C403.2 and C403.3, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
2. The total cooling capacity of all of the cooling systems is nearly 755 MBH. Explain why economizers should not be provided to limit the total cooling capacity without economizers to less than 300 MBH for the building. Reference: Section C403.3.1, IECC 2012.
3. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
4. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated. Reference: Section 403.2.1 (4), IMC 2012.
05/22/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/22/2013 ROBERT SHERRY WATER REVIEW Approved
05/22/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved 1. PROVIDE STRUCTURAL CALCULATIONS FOR ALL NEW ROOD TOP MOUNTED HVAC UNITS.
05/22/2013 GERRY KOZIOL WWM REVIEW Approved
05/22/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide backflow protection for the directly-connected testing equipment
05/22/2013 JASON GREEN ENGINEERING REVIEW Approved
05/22/2013 MARTIN BROWN FIRE REVIEW Approved
05/22/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed