06/18/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM03093
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FOUNDATION PLANS:

1. Show compliance with termite treatment, R320.

SECTIONS - DETAILS:

1. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, 2012 IRC, R702.4.2. Update note #6/A1.

PLUMBING PLANS:

1. When specifying a gray drain line with a diverter valve, show a complete collection and discharge system consistent with P3009.

ELECTRICAL PLANS:

1. Notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
2. Provide a panel schedule showing consistent wire size (circuit #1,3) for the 100A sub panel feeder, E3602.2.
3. Show or notate a disconnect means or a locking breaker for the water heater, E4001.5.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and walls R=13. Mass wall requirement is R=4 when 50% of insulation is exterior and R=6 when applied interior, N1102.1. Show a means of achieving the prescriptive values at each assembly, or show overall compliance if using less than prescribed component values by providing a RES check calculation.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review