Permit Number: T13CM03089
Parcel: 13323190A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM03089
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the plan views for detail PSD-7/P6.1 to show the drains running independently to the floor sink. [Previous comments: Comment not addressed. Revise the drains for the 3-compartment sink (as shown in the plan views of detail PSD-7/P6.1) to be independently routed to the indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC.]
2. The relocated sink shall be directly-connected to the sanitary drain system. Reference: Section 802.1, IPC 2012.