Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM03089
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/25/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the plan views for detail PSD-7/P6.1 to show the drains running independently to the floor sink. [Previous comments: Comment not addressed. Revise the drains for the 3-compartment sink (as shown in the plan views of detail PSD-7/P6.1) to be independently routed to the indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC.] 2. The relocated sink shall be directly-connected to the sanitary drain system. Reference: Section 802.1, IPC 2012. |