Permit Number: T13CM03089
Parcel: 13323190A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM03089
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not addressed. Revise the drains for the 3-compartment sink (as shown in the plan views of detail PSD-7/P6.1) to be independently routed to the indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC.
06/13/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2013 CPIERCE1 REJECT SHELF Completed