Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM03089
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/22/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/23/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/23/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the drains for the 3-compartment sink (as shown in the plan views of detail PSD-7/P6.1) to be independently routed to the indirect waste receptor and terminated with an air gap. Reference: Sections 801.2 and 802.1, IPC. |
| 05/23/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/23/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 05/30/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/04/2013 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 06/04/2013 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |