Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T13CM03088
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/13/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | P&DS TRANSMITTAL FROM: Michael St.Paul, Planning Technician PROJECT: T13CM03088 2845 North Swan Road Addition to SFR TRANSMITTAL: September 13, 2013 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The height of the proposed addition facing the south property line is thirteen (13) feet, six (6) inches. The required setback is nine (9) feet. The proposed setback to the south property line is one (1) foot. |
| 09/13/2013 | JASON GREEN | ENGINEERING | REVIEW | Needs Review | |
| 09/13/2013 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Needs Review | |
| 09/16/2013 | GERRY KOZIOL | WWM | REVIEW | Completed | |
| 09/16/2013 | SPOWELL1 | NPPO | REVIEW | Needs Review |