Permit Number: T13CM03037
Parcel: 137055240

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM03037
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 5: IBC SECTION 2902.3.1 INDICATES A PUBLIC TOILET SHALL NOT PASS THROUGH STORAGE ROOMS.
2. PREVIOUS COMMENT 6: ADD A NORTH ARROW TO SHEET A-1.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/05/2013 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review