05/23/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM03037
1217 W Irvington #111
Dress Barn

1. Please clarify the following on the Interior Lighting and Power Compliance Certificate:
a. Cover sheet indicates square footage of building is
7015 sq ft, the Report shows 8005 sq ft ?
b. is the method to be used total bldg sq footage or space by space ? Indicate where the "Allowance for 1000 sq ft @ 2.6 watts /sq ft" is obtained, and 'supplemental Allowance of 1000 watts obtained ?

Ray T Majuta
Elect Plan Review
PDSD, Tucson,
5/23/2013
Ray.Majuta@tucsonaz.gov