Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM03037
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM03037 1217 W Irvington #111 Dress Barn 1. Please clarify the following on the Interior Lighting and Power Compliance Certificate: a. Cover sheet indicates square footage of building is 7015 sq ft, the Report shows 8005 sq ft ? b. is the method to be used total bldg sq footage or space by space ? Indicate where the "Allowance for 1000 sq ft @ 2.6 watts /sq ft" is obtained, and 'supplemental Allowance of 1000 watts obtained ? Ray T Majuta Elect Plan Review PDSD, Tucson, 5/23/2013 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/03/2013 | GERARDO BONILLA | APPROVAL SHELF | Completed |
| 06/03/2013 | CPIERCE1 | REJECT SHELF | Completed |