Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM03037
Parcel: 137055240

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM03037
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
05/20/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
05/20/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/20/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET CV-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE 3/32" IN HEIGHT MINIMUM. REVISE THE GENERAL NOTES.
2. SHEET A-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE 3/32" IN HEIGHT MINIMUM. REVISE THE FLOOR PLAN NOTES AND DIMENSIONS.
3. SHEET A-1; LEGEND: INCLUDE ON THE NEW PARTITION WALL THAT THE SHEET ROCK IS TYPE X.
4. SHEET A-1; FLOOR PLAN: DOES THE EXISTING REAR DOOR EXIT HAVE SIGNAGE? VERIFY.
5. SHEET A-1; FLOOR PLAN: DOES THE DOOR FROM THE CORRIDOR (AT THE NORTHWEST CORNER) INTO THE STOCK ROOM AREA LOCK? IS THAT RESTROOM ACCESSIBLE THROUGH THAT DOOR? VERIFY.
6. GENERAL: PROVIDE A NORTH ARROW ON THE PLANS.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/20/2013 KEN BROUILLETTE FIRE REVIEW Approved
05/20/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/21/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation using the current code; ASHRAE 62.1-2007 is not acceptable. Reference: Section 403.2, IMC 2012.
2. Ventilation calculations shall be based upon the net occupiable floor area. Store fixtures, furnishings, display racks and other obstructions shall not be deducted from the net occupiable floor area. Reference: Section 202, IMC 2012.
3. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated (i.e. the fans shall operate whenever the HVAC system delivers air into the restrooms). Reference: Section 403.2.1 (4), IMC 2012.
05/21/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/21/2013 ROBERT SHERRY WATER REVIEW Approved
05/21/2013 FRODRIG2 WWM REVIEW Passed