Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM03037
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/20/2013 | LAITH ALSHAMI | ENGINEERING | REVIEW | Approved | |
| 05/20/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/20/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET CV-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE 3/32" IN HEIGHT MINIMUM. REVISE THE GENERAL NOTES. 2. SHEET A-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE 3/32" IN HEIGHT MINIMUM. REVISE THE FLOOR PLAN NOTES AND DIMENSIONS. 3. SHEET A-1; LEGEND: INCLUDE ON THE NEW PARTITION WALL THAT THE SHEET ROCK IS TYPE X. 4. SHEET A-1; FLOOR PLAN: DOES THE EXISTING REAR DOOR EXIT HAVE SIGNAGE? VERIFY. 5. SHEET A-1; FLOOR PLAN: DOES THE DOOR FROM THE CORRIDOR (AT THE NORTHWEST CORNER) INTO THE STOCK ROOM AREA LOCK? IS THAT RESTROOM ACCESSIBLE THROUGH THAT DOOR? VERIFY. 6. GENERAL: PROVIDE A NORTH ARROW ON THE PLANS. 7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/20/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 05/20/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/21/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation using the current code; ASHRAE 62.1-2007 is not acceptable. Reference: Section 403.2, IMC 2012. 2. Ventilation calculations shall be based upon the net occupiable floor area. Store fixtures, furnishings, display racks and other obstructions shall not be deducted from the net occupiable floor area. Reference: Section 202, IMC 2012. 3. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted with no more than 10% exhausted air being recirculated (i.e. the fans shall operate whenever the HVAC system delivers air into the restrooms). Reference: Section 403.2.1 (4), IMC 2012. |
| 05/21/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/21/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/21/2013 | FRODRIG2 | WWM | REVIEW | Passed |