Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM02998
3940 E Timrod St
Service Upgrade 1-400amp and 1-600amp

1. East Side Service with 6 meters- 6 units: if existing wireway above service is outdoors will have to be replaced with Nema 3R wireway.
Provide fault current values and how and where brought to 10K AIC or below.
2. West Side Service shows 6 meters only, one being a HP(House Panek).There are 11 units assigned to this service how will they be metered ? This information necessary in order for clearance to Utility. Notation to left of service indicates a 60 amp disconnect to be added for the AC to units, will this be for 11 units ?
If the existing wireway above this service is outdoors, the wireway will have to be Nema 3R.
Provide a load calculation on this service due to 4- 200 amp
meters, 2-100 amp meters, which includes 11 possible 60 amp AC disconnects, 2-200 amp disconnects to the right of the service for existing loads. Also provide fault current values at service bringing the value to 10K AIC or below.

Ray Majuta
Elect Plan Review,
PDSD, Tuc,
5/20/2013