Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM02982
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE A STRUCTURAL ANALYSIS OF THE EXISTING ROOF STRUCTURE UNDER THE LOADING OF THE NEW UNITS. |
| 05/16/2013 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/16/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 05/16/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations using the 2012 IMC. 2. Show how relief will be provided during economizer operation for the south building and for the common areas in both buildings. |
| 05/16/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 05/30/2013 | FRODRIG2 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/30/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |