Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM02975
Parcel: 11706168A

Address:
33 S 5TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02975
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2013 MARTIN BROWN FIRE REVIEW Approved
05/28/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A3.2
1. An accessible route slope of 1:20 and greater is not a ramp. Delete the ramp term on the sloped sidewalk south and west of the elevator.
2, Provide handrails at the long stair with 4 risers and 3 treads as per the 2012 IBC, Section 1009.15 and 1012.9.
SHEET A6.2
3. At detail 6, provide handrails.
SHEET A7.0
4. Details 38 and 39/A9.2 do not exist. Make some details.
SHEET A3.3 AND A7.0
5. Extend the wood stair handrails 12" beyond the last riser.
SHEET A8.6
6. Detail 68: sink to be mounted 2'-10" a.f.f.
SHEET A8.7
7. Identify the accessible urinal.
8. Provide accessible showers as per the 2009 Edition, ICC A117.1, Section 608.
SHEET A9.1
9. Detail 22: Provide height a.f.f. dimensions.
SHEET A9.2
10. Please finish this sheet.
SHEET A3.2
11. Show detail of Vintage Typewriter installation.
12. At the ramps that lead down from the new raised reception floor, note reference 4 indicates "new concrete, reference structural details". There are no structural details on the structural sheets for these concrete ramps. Please reconcile.
SHEET S1.1
13. Provide certification for special inspectors as outlined on this sheet.
SHEET S2.0
14. Please show the concrete ramp details.
15. Providfe structural calculations and details for all new and relocated fan coil units and new roof top mounted heat pumps.
END OF REVIEW
06/05/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012.
2. Show how ventilation is being provided for the areas served by FC-7 and FC-8. Reference: Section 401.3, IMC 2012.
3. Show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference: 401.4, IMC 2012.
4. Show that the proposed new HVAC system meets the requirements of Sections C403.2, C403.3 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
06/05/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the plumbing fixture specification for the lavatories; is P1 the same as P1B?
2. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Sections 416.5, 607.1 a, IPC 2012 and Section C404.3, IECC 2012.
3. Provide a cleanout at the base of each waste stack (detail 5/P2.1). Reference: Section 708.3.4, IPC 2012.
06/05/2013 ROBERT SHERRY WATER REVIEW Approved
06/05/2013 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve the building plan until a development package has been submitted and approved.
06/12/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM02975
33 S 5 th av
Connect

1. E1.0, Item # 19 under Keyed Notes, provide a panel schedule for panel A, show load and location. (55 Fixtures).
2. E1.1, Item # 3 under Keyed Notes same as item above.
Circuit has 52 fixtures.
3. E 2.0, Item 40 under Keyed Notes same as item # 1.
4. E 3.0, Fault current at Panel PE1 showing a value of 10K AIC, value of at panel is 42,592 AIC.
5. E 5.0, FACP shows going to HP 9, where is this located ?

Ray Majuta
Elect Plan Review
PDSD, Tucson
6/13/2013
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/18/2013 CPIERCE1 REJECT SHELF Completed