Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM02975
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/22/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/28/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEET A3.2 1. An accessible route slope of 1:20 and greater is not a ramp. Delete the ramp term on the sloped sidewalk south and west of the elevator. 2, Provide handrails at the long stair with 4 risers and 3 treads as per the 2012 IBC, Section 1009.15 and 1012.9. SHEET A6.2 3. At detail 6, provide handrails. SHEET A7.0 4. Details 38 and 39/A9.2 do not exist. Make some details. SHEET A3.3 AND A7.0 5. Extend the wood stair handrails 12" beyond the last riser. SHEET A8.6 6. Detail 68: sink to be mounted 2'-10" a.f.f. SHEET A8.7 7. Identify the accessible urinal. 8. Provide accessible showers as per the 2009 Edition, ICC A117.1, Section 608. SHEET A9.1 9. Detail 22: Provide height a.f.f. dimensions. SHEET A9.2 10. Please finish this sheet. SHEET A3.2 11. Show detail of Vintage Typewriter installation. 12. At the ramps that lead down from the new raised reception floor, note reference 4 indicates "new concrete, reference structural details". There are no structural details on the structural sheets for these concrete ramps. Please reconcile. SHEET S1.1 13. Provide certification for special inspectors as outlined on this sheet. SHEET S2.0 14. Please show the concrete ramp details. 15. Providfe structural calculations and details for all new and relocated fan coil units and new roof top mounted heat pumps. END OF REVIEW |
06/05/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012. 2. Show how ventilation is being provided for the areas served by FC-7 and FC-8. Reference: Section 401.3, IMC 2012. 3. Show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference: 401.4, IMC 2012. 4. Show that the proposed new HVAC system meets the requirements of Sections C403.2, C403.3 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012. |
06/05/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the plumbing fixture specification for the lavatories; is P1 the same as P1B? 2. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Sections 416.5, 607.1 a, IPC 2012 and Section C404.3, IECC 2012. 3. Provide a cleanout at the base of each waste stack (detail 5/P2.1). Reference: Section 708.3.4, IPC 2012. |
06/05/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/05/2013 | TERRY STEVENS | ZONING | REVIEW | Denied | Zoning cannot approve the building plan until a development package has been submitted and approved. |
06/12/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM02975 33 S 5 th av Connect 1. E1.0, Item # 19 under Keyed Notes, provide a panel schedule for panel A, show load and location. (55 Fixtures). 2. E1.1, Item # 3 under Keyed Notes same as item above. Circuit has 52 fixtures. 3. E 2.0, Item 40 under Keyed Notes same as item # 1. 4. E 3.0, Fault current at Panel PE1 showing a value of 10K AIC, value of at panel is 42,592 AIC. 5. E 5.0, FACP shows going to HP 9, where is this located ? Ray Majuta Elect Plan Review PDSD, Tucson 6/13/2013 Ray.Majuta@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/18/2013 | CPIERCE1 | REJECT SHELF | Completed |