Permit Number: T13CM02951
Parcel: 13415001F

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM02951
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2013 RONALD BROWN ADA REVIEW Passed
06/04/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/12/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/12/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/13/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM02951
7750 E Broadway Bl
346.33KW DC Photovoltaic System

1. Sheet PV2.1, the total DC kw value for P1A array is listed as 17.248kw should be 19.712kw. The 8 modules at 308w
at 8 arrays = 19.712kw.
2. Sheet PV2.1, the total DC kw value for PB3 array is listed as 36.624kw should be 20.601kw.
3. Sheet PV2.0 shows 350 amp fuses in the 600 amp (AC) fused disconnect prior to going to the 1600 amp service, sheet PV2.2 shows 450 amp fuses in the 600 amp (AC) disconnect.
4. The existing 1600 amp switchgear will require certification by third party OSHA Recognized Testing Laboratory (not manufacture of switchgear) regarding the installation of new conductors from the PV system. Cannot be verified if this installation will comply with what the existing switchgear was made to allow.Please indicate this on sheet PV2.0 next to location of gear.
This information to be made available to AHJ Inspector prior to re-energizing switchgear and start up of PV System.
Please indicate this on sheet PV2.0 next to location of switchgear.


Ray Majuta
Electrical Plan Review
PDSD, Tucson
6/14/2013
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2013 CPIERCE1 REJECT SHELF Completed