Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM02951
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2013 | RONALD BROWN | ADA | REVIEW | Passed | |
| 06/04/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/12/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/12/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/13/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM02951 7750 E Broadway Bl 346.33KW DC Photovoltaic System 1. Sheet PV2.1, the total DC kw value for P1A array is listed as 17.248kw should be 19.712kw. The 8 modules at 308w at 8 arrays = 19.712kw. 2. Sheet PV2.1, the total DC kw value for PB3 array is listed as 36.624kw should be 20.601kw. 3. Sheet PV2.0 shows 350 amp fuses in the 600 amp (AC) fused disconnect prior to going to the 1600 amp service, sheet PV2.2 shows 450 amp fuses in the 600 amp (AC) disconnect. 4. The existing 1600 amp switchgear will require certification by third party OSHA Recognized Testing Laboratory (not manufacture of switchgear) regarding the installation of new conductors from the PV system. Cannot be verified if this installation will comply with what the existing switchgear was made to allow.Please indicate this on sheet PV2.0 next to location of gear. This information to be made available to AHJ Inspector prior to re-energizing switchgear and start up of PV System. Please indicate this on sheet PV2.0 next to location of switchgear. Ray Majuta Electrical Plan Review PDSD, Tucson 6/14/2013 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/05/2013 | CPIERCE1 | REJECT SHELF | Completed |