Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T13CM02916
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 06/06/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/12/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a site plan showing the continuation and termination of the proposed building sewer and HCS connection. 2. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. |
| 06/12/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/12/2013 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a site plan showing the location of the proposed 1-1/2" water meter and the proposed 2" reduced pressure backflow preventer. |
| 06/17/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T13cm02916 5315 S Calle Santa Cruz New Shell Bldg 1. Sheet E1.0, indicates the 2005 NEC is to be complied with, needs to be 2011 NEC. 2. Sheet E2.0, the primary service entrance conductors (utility to 1200 amp CT) to indicate 3 sets of parallel feeds rather than 2 sets ? Ray T Majuta Elect Plan Review PDSD, Tucson 6/17/2013 Ray.Majuta@tucsonaz.gov |
| 06/19/2013 | DAVID RIVERA | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/19/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Approved |