Permit Number: T13CM02860
Parcel: 10408090D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02860
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G100; APPLICABLE CODES: THE ACCESSIBILITY CODE FOR THE CITY OF TUCSON IS THE ICC/ANSI A117.1-2009. REVISE ON THE DRAWING.
2. SHEET G100: PROVIDE A CODE ANALYSIS ON THIS SHEET, INCLUDING THE OCCUPANCY GROUP, CONSTRUCTION TYPE, AND OCCUPANCY SQUARE FOOTAGE.
3. SHEET G101; DETAIL 35/G102: PROVIDE A VERTICAL GRAB BAR AT THE WATER CLOSET PER THE ICC/ANSI A117.1-2009, FIGURE 604.5.1.
4. SHEET G101: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE DETAILS AND TITLES.
5. SHEET A300; RESTROOM ELEVATIONS: INDICATE THE VERTICAL GRAB BAR ON THE ELEVATIONS.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. SUBSEQUENT REVIEWS WILL NOT BE PERFORMED WITHOUT RESPONSES.
05/13/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/13/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM02860

Provide an updated panel schedule showing current loads, show location of panel, assign circuit numbers to lighting
circuits along with panel designations.

Ray Majuta
El Plan Ck
5/13/13
05/13/2013 ROBERT SHERRY WATER REVIEW Denied Provide the sizes of the water meter and the backflow preventer serving this building.
05/13/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/13/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
05/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the extent of the plumbing work
05/14/2013 KEN BROUILLETTE FIRE REVIEW Denied 1. SHEET G100: PROVIDE A CODE ANALYSIS ON THIS SHEET, INCLUDING THE OCCUPANCY GROUP, CONSTRUCTION TYPE, OCCUPANCY SQUARE FOOTAGE, AND TOTAL OCCUPANT LOAD.
2. INDICATE ON PLANS WHETHER OR NOT A FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM EXISTS, AND IF ALTERATIONS TO THESE SYSTEMS ARE PLANNED UNDER SEPARATE SUBMITTAL.
06/24/2013 CPIERCE1 WWM REVIEW Needs Review
06/24/2013 CPIERCE1 ZONING REVIEW Needs Review