Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/20/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the fan-filter units are being supported in accordance with the conditions of its listing and the manufacturer's installation requirements. Reference: Section 304.1, IMC 2012.
2. Verify the ventilation calculations for the pump alley; how is it more like an office than a mechanical room?
3. Show how adequate make-up air (supply air plus transfer air) is to be provided to room 102 so that the room pressure remains essentially neutral. Reference: Section 501.4, IMC 2012.
4. Verify that the fan-filter units are suitable for installation in a plenum. Reference: Section 602.2.1, IMC 2012.