Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM02816
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/20/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/20/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the fan-filter units are being supported in accordance with the conditions of its listing and the manufacturer's installation requirements. Reference: Section 304.1, IMC 2012. 2. Verify the ventilation calculations for the pump alley; how is it more like an office than a mechanical room? 3. Show how adequate make-up air (supply air plus transfer air) is to be provided to room 102 so that the room pressure remains essentially neutral. Reference: Section 501.4, IMC 2012. 4. Verify that the fan-filter units are suitable for installation in a plenum. Reference: Section 602.2.1, IMC 2012. |