Permit Number: T13CM02816
Parcel: 140420270

Address:
2650 E ELVIRA RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02816
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2013 STEVE SHIELDS ZONING REVIEW Approved
05/09/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
05/09/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/09/2013 ROBERT SHERRY WATER REVIEW Denied Provide the size of both the water service meter and the reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2012.
05/09/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; DEMOLITION KEYNOTES: NOTES 5 AND 7 WERE NOT LOCATED ON THE PLAN. VERIFY.
2. SHEET A2.0; DETAIL 6: PROVIDE THE CONNECTOR SIZE FOR THE TIE WIRE TO THE ROOF STRUCTURE AND TO THE TOP OF THE PARTITION.
3. SHEET A2.0; KEYNOTES: NOTE 10 WAS NOT LOCATED ON THE PLAN. VERIFY.
4. GENERAL: PROVIDE STRUCTURAL CALCULATIONS.
5. SHEET S2.1: COLUMN C2 (FROM SHEET S1.3) WAS NOT LOCATED ON THE PLANS. VERIFY.
6. SHEET S3.1: DETAIL CUT 103 WAS NOT LOCATED ON THE PLANS ON SHEET S2.1. VERIFY.
7. SHEET S3.1; DETAILS 202 AND 203: WHERE DOES THE HSS 6X2 (SHOWN IN DETAIL 202) END AND THE HSS 8X2 (SHOWN IN DETAIL 203) BEGIN? CLARIFY.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/09/2013 LOREN MAKUS ENGINEERING REVIEW Approved
05/09/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012.
2. Clarify the nature of the "treatment tank". Provide material standards for the tank and show how it is to be drained.
3. Provide specifications for the pumps located by the hand sinks and provide a detail shoe.
4. Provide the material standards for the water service and water distribution piping materials and fittings. Reference: Sections 605.3 and 605.5, IPC 2012.
5. Specify the materials to be used for the drainage piping and fittings. Reference: Section 702, IPC 2012.
05/09/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/10/2013 MARTIN BROWN FIRE REVIEW Approved
05/16/2013 CPIERCE1 WWM REVIEW Needs Review