Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM02815
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/21/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/23/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | PANIC HARDWARE REQUIRED ON EGRESS DOORS |
| 05/23/2013 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/28/2013 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1) CLARIFY HOW ALL WATER CLOSET COMPARTMENTS ARE TO BE EXHAUSTED. EF-1 AND EF-2 ARE PLACED IN TOILET COMPARTMENTS ENCLOSED BY FULL HEIGHT WALLS WITH FULL SIZE DOORS PER ARCHITECTURAL PAGES. 2) PROVIDE SEQUENCE OF OPERATION WITH AHU-3 AND EF-1, EF-2 FOR NON-RECIRCULATION OF AIR (IMC 403.2.1). MECHANICAL NOTES CALL FOR ELECTRICIAN INTERLOCK, BUT ELECTRICAL SHEETS HAVE EF'S CONNECTED TO OCCUPANCY SENSOR. 3) Please check off appropriate boxes for review of IECC compliance certificate |
| 05/28/2013 | LHANLY1 | WATER | REVIEW | Approved | |
| 05/28/2013 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1) Fixture & connection schedule is calling for 1/2" supply to wc flushometers, please revise to 1". 2) Provide developed lengths of gas lines. Rough scaling from plans indicates undersized supply line just downstream of 1st gh1. Revisions to the plumbing plans may be made by hand on plan set if engineer allows. Contact LeeRay @ 909-5154 for questions. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/13/2013 | CPIERCE1 | REJECT SHELF | Completed |