Permit Number: T13CM02815
Parcel: 11706175A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02815
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/23/2013 KEN BROUILLETTE FIRE REVIEW Approv-Cond PANIC HARDWARE REQUIRED ON EGRESS DOORS
05/23/2013 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
05/28/2013 LHANLY1 WATER REVIEW Approved
05/28/2013 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Reqs Change 1) Fixture & connection schedule is calling for 1/2" supply to wc flushometers, please revise to 1".

2) Provide developed lengths of gas lines. Rough scaling from plans indicates undersized supply line just downstream of 1st gh1.

Revisions to the plumbing plans may be made by hand on plan set if engineer allows. Contact LeeRay @ 909-5154 for questions.
05/28/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1) CLARIFY HOW ALL WATER CLOSET COMPARTMENTS ARE TO BE EXHAUSTED. EF-1 AND EF-2 ARE PLACED IN TOILET COMPARTMENTS ENCLOSED BY FULL HEIGHT WALLS WITH FULL SIZE DOORS PER ARCHITECTURAL PAGES.

2) PROVIDE SEQUENCE OF OPERATION WITH AHU-3 AND EF-1, EF-2 FOR NON-RECIRCULATION OF AIR (IMC 403.2.1). MECHANICAL NOTES CALL FOR ELECTRICIAN INTERLOCK, BUT ELECTRICAL SHEETS HAVE EF'S CONNECTED TO OCCUPANCY SENSOR.

3) Please check off appropriate boxes for review of IECC compliance certificate

Final Status

Task End Date Reviewer's Name Type of Review Description
06/13/2013 CPIERCE1 REJECT SHELF Completed