Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM02808
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/05/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/05/2013 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/05/2013 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/05/2013 | GERRY KOZIOL | WWM | REVIEW | Approved |