Permit Number: T13CM02805
Parcel: 12213045A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02805
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
05/09/2013 JASON GREEN ENGINEERING REVIEW Approved
05/09/2013 MARTIN BROWN FIRE REVIEW Approved
05/15/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Verify the supply air flow rates for the two restrooms does not exceed the exhaust flow rates for each room.
05/15/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Show Water Heaters, circuits, updated panel schedule and location.

Ray Majuta
5/15/2013
05/15/2013 ROBERT SHERRY WATER REVIEW Denied Provide the size of the water meter and its associated backflow preventer.
05/15/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET GN-1; DEAD END CORRIDOR: REFERENCE THE IBC SECTION 1018.4. THE MAXIMUM DISTANCE FOR AN UNSPRINKLERED SPACE IS 20 FEET.
2. SHEET A-1; FLOOR PLAN: THE STALL IN THE MEN'S RESTROOM DOES NOT APPEAR TO MEET ICC/ANSI A117.1-2009 REQUIREMENTS PER CHAPTER 3. VERIFY.
3. SHEET A-1; FLOOR PLAN: THE DOOR SWING IN THE MEN'S RESTROOM STALL MUST MEET THE ICC/ANSI REQUIREMENTS PER FIGURE 604.9.3.1.
4. SHEET A-1: INDICATE ON A DETAIL THE GRAB BAR LOCATIONS AND LENGTHS PER THE ICC/ANSI FIGURE 604.5.1.
5. SHEET A-2; PARTITION TYPES: REVISE THE DETAIL WITH THE DIAGONAL BRACING. INDICATE THE CONNECTION BRACE TO THE STRUCTURE ABOVE. INCLUDE THE BRACE SIZE, CONNECTION SIZES, AND CONNECTION QUANTITIES.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/15/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide specifications for the plumbing fixtures and the water heaters.
2. Provide cleanouts equal in size to the drain pipes.
3. The minimum size for the water supply to the urinal is 3/4"
4. Verify the water pipe sizes.
05/15/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/22/2013 SPOWELL1 WWM REVIEW Needs Review