Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM02805
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/09/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/09/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/15/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Verify the supply air flow rates for the two restrooms does not exceed the exhaust flow rates for each room. |
| 05/15/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Show Water Heaters, circuits, updated panel schedule and location. Ray Majuta 5/15/2013 |
| 05/15/2013 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the size of the water meter and its associated backflow preventer. |
| 05/15/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET GN-1; DEAD END CORRIDOR: REFERENCE THE IBC SECTION 1018.4. THE MAXIMUM DISTANCE FOR AN UNSPRINKLERED SPACE IS 20 FEET. 2. SHEET A-1; FLOOR PLAN: THE STALL IN THE MEN'S RESTROOM DOES NOT APPEAR TO MEET ICC/ANSI A117.1-2009 REQUIREMENTS PER CHAPTER 3. VERIFY. 3. SHEET A-1; FLOOR PLAN: THE DOOR SWING IN THE MEN'S RESTROOM STALL MUST MEET THE ICC/ANSI REQUIREMENTS PER FIGURE 604.9.3.1. 4. SHEET A-1: INDICATE ON A DETAIL THE GRAB BAR LOCATIONS AND LENGTHS PER THE ICC/ANSI FIGURE 604.5.1. 5. SHEET A-2; PARTITION TYPES: REVISE THE DETAIL WITH THE DIAGONAL BRACING. INDICATE THE CONNECTION BRACE TO THE STRUCTURE ABOVE. INCLUDE THE BRACE SIZE, CONNECTION SIZES, AND CONNECTION QUANTITIES. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/15/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide specifications for the plumbing fixtures and the water heaters. 2. Provide cleanouts equal in size to the drain pipes. 3. The minimum size for the water supply to the urinal is 3/4" 4. Verify the water pipe sizes. |
| 05/15/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/22/2013 | SPOWELL1 | WWM | REVIEW | Needs Review |