Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM02705
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/15/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | The 55 gallon water heater is shown on plumbing detail 3/P1 as being mounted on the floor. However, detail 5/A5.1 shows an above floor, shelf mounted water heater. Please reconcile these differences and if the water heater is to be mounted above the floor on a shelf, please provide structural calculations as to the stability of the shelf design. |
| 05/21/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/21/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the water pressure calculations using the minimum available water pressure; according to the data for the shell building, the minimum water pressure is 46 PSI, not 56 PSI. Verify the sizes for the water distribution system. Reference: Section A1.1, UPC 2012. 2. A restaurant is an assembly occupancy. Revise the fixture unit and demand calculations using the "assembly" values for the water closets and the urinal. Reference: Table A2.1, UPC 2012. 3. Detail 3/P3 calls for the drain pan under the floor-mounted water heater and the flue condensate drain to terminate at the adjacent mop sink. The specified mop sink has a 10"-high rim; will the water heater be mounted on a platform? 4. Verify the developed pipe lengths for the natural gas service to K20, K20B, and the two K22 units. Reference: Section 402.4, IFGC 2012. |
| 05/22/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations for AC-1 to include an occupant density of 100 people per 1,000 square feet per Table 403.3, IMC 2012. Reference: Section 403.3, IMC 2012. |
| 05/23/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/23/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |