Permit Number: T13CM02682
Parcel: 13323193C

Address:
750 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02682
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS.1; SHEET INDEX: SHEETS S.1 AND S.2 ARE LISTED ON THE INDEX, BUT NOT INCLUDED IN THE SET. PROVIDE.
2. SHEET TS.1; PROJECT DATA: UNDER THE OCCUPANCY, AN ENCLOSED PATIO IS INCLUDED IN THIS PROJECT. WHERE ARE THE PATIO AND DETAILS SHOWN, OR IS IT EXISTING? VERIFY.
3. SHEET A.1; FLOOR PLAN: INDICATE A NORTH ARROW ON THE PLAN.
4. SHEET A.1; FLOOR PLAN: THE COLUMN AT THE MAIN ENTRY TRELLIS CAN NOT BE IN THE SLOPE OF THE HANDICAP RAMP. REVISE.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/03/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
05/06/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/06/2013 KEN BROUILLETTE FIRE REVIEW Approved
05/13/2013 LOREN MAKUS ENGINEERING REVIEW Approved
05/17/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the exposed water pipes are to be protected from freezing. Reference: Section 305.4, IPC 2012
2. The developed length of the revised hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012.
3. Show how combustion and dilution air is being provided for the water heater and the dryer. Reference: Section 304, IFGC 2012.
05/17/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/17/2013 ROBERT SHERRY WATER REVIEW Approved
05/29/2013 CPIERCE1 ZONING REVIEW Needs Review
05/29/2013 CPIERCE1 WWM REVIEW Needs Review