Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM02638
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/13/2013 | MARTIN BROWN | FIRE | REVIEW | Denied | Initial fire department review denial comments not addressed in response letter. |
11/13/2013 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Carl's Jr @ 7632 S. Wilmot T13CM02638 Building Plan (2nd Review) TRANSMITTAL DATE: November 13, 2013 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plans until the development package has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
11/15/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/21/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM02638 7638 S Wilmot RD Carl's Restaurant 1. Sheet E5, the fault current at the utility transformer per Tucson Electric Service Requirement Book for a 600 amp 120/208 volt pad mounted transformer feed is listed as 55,600 amps, sheet E5 shows 8979.10 amps ? 2. Sheet E2, note #2, "all exterior Light Fixtures shall be controlled by a photocell not a timeclock." The 2012 City of Tucson Outdoor Lighting Code Section 403.1--"all unshielded lighting to be extingushied between 11 PM and sunrise next day."This is to be accomplished by a 24 hour timing device per Section 403.5. Please review Section 403 of The C of T ODLC. Ray T Majuta Elect Plan Review PDSD, Tucson 11/25/2013 Ray.majuta@tucsonaz.gov 520-837-4988 |
12/02/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/02/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The site utilities plan, MEP-1, the plumbing plan, P1, and the civil utilities plan, C7 are not close to being coordinated. There are three different points of entry to the building shown on the three drawings for the natural gas, the domestic water, the grease waste, and the sanitary waste. The civil plans also show the size of the water service to be 1-1/2" compared to the 2" shown on P1 and both the grease waste and the sanitary waste are 6" on the civil plans compared to the 4" shown on P1. The site plan, MEP-1 has the north arrow pointed due west and the vicinity map on sheet T-1 shows the property to be located on the east side of South Wilmot Road and north of I-10 even though the property is actually located south of I-10 along the west side of South Wilmot Road. Coordinate the plans and include the civil utility plans as part of the building plan set; the construction of the on-site utilities must be included as part of a building permit |
12/03/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Keynote 7 on sheet M1 and the grease duct note on sheet M3 direct the contractor to "Coordinate required fire rated enclosure of kitchen hood exhaust as per NFPA and IMC". No design is shown on the drawings; provide a design for the contractor to install an approved grease duct enclosure per Section 506.3.11, IMC 2012. A grease duct serving a Type I hood, but not wrapped with a fire-resistive material meeting the requirements of ASTM E 2336 (Section 506.3.11.2, IMC 2012) or constructed of a factory-built grease duct assembly listed and labeled for use in accordance with UL-2221 (Section 506.3.11.3, IMC 2012), shall be enclosed within a duct enclosure constructed in accordance with Section 506.3.11.1, IMC 2012. 2. The griddle hood and the fryer hood are supported on the exterior walls of the building. The walls are built with wood studs. Unless the hoods are listed for zero-clearance to combustibles, revise the installation of the hood to provide 18" of clearance between the hood and combustible construction (note that wood studs covered by gypsum board and a sheet of stainless steel are considered combustible construction by the IMC). Reference: Section 507.9, IMC 2012; see also Section 507.10, IMC 2012. 3. The revised detail (3/M3) shows the exhaust fan supported on a wooden curb. Per Section 506.4, IMC 2012, exhaust equipment shall have a clearance to combustibles of not less than 18". In addition, the minimum height of the discharge opening of the fan shall be at least 40" above the surface of the roof. [Initial comment: Show that the outlet of fans EF-2 and EF-3 comply with the requirements of Section 506.5.5, IMC 2012.] |
12/11/2013 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Denied | Engineering will approve/stamp once grading is approved. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/12/2014 | CPIERCE1 | REJECT SHELF | Completed |