Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM02637
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the mechanical plans based on the submitted mechanical compliance certificate: 1. The minimum EER is to be 11.0, not 10.3 2. Provide a method to relieve the excees air from the building. 3. Verify that the automatic controls provide for setback to 55 F (heating), 85F (cooling), 2-hour occupant override, and a 10-hour back up. 4. The controls shall provide an automatic start capability that can automatically adjust the daily start time for the HVAC units. |