Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM02629
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/04/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/04/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. See referenced code sections for resolving this comment. [Initial comment: Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Sections 416.5, 607.1 and 607.1.2, IPC 2012 and Section C404.3, IECC 2012.] 2. The material specifications allow the use of ABS in the plenum, a combustible material. [Initial comment: Materials exposed in plenums shall conform to Section 602.2.1, IMC 2012.] |
06/04/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |