Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM02598
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2013 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 05/01/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/01/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM02598 1. Insert into application individual unit numbers, 1 thur14, 32 also House Panel, these will all have to be cleared to Utility and unit numbers are required. 2. Sheet E-4 Service Load Calculations, the total square footage for units is 8767 sf as taken per panel schedule rather than 2922 sf used ? 3. IBC 2012, 907.2.11.2 requires smoke detectors in the units.Unsure if these will be covered by the "Code Upgrade Requirements" on cover sheet, under Fire Alarm System, Design and Plan by Others. Please verify. 4. Verify TEP to accept Main Disconnect ahead of Metering. Ray T Majuta Elect Plan Review DSD, C of Tucson, 5/1/2013 Ray.Majuta@tucsonaz.gov |
| 05/01/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/01/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/01/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 05/01/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/01/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/01/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/02/2013 | FRODRIG2 | WWM | REVIEW | Passed |