Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the listing information for the induction range being installed in the Servery/Prep room (1129) and provide justification for not locating the range under a Type I hood. Reference: Section 507.2.1, IMC 2012.
2. Clarify how exhaust fan EF-29 provides the required exhaust for the appliances located in rooms 1128 and 1129 that are not required to be located under a Type II hood.
3. Revise the mechanical design as required to avoid using corridors as return air ducts (see rooms 1123, 1126, 1147, 1148, and 1149). Reference: Section 601.2, IMC 2012.
08/30/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the size of the fixture drain for the mat wash (sheet P1.1).
2. Clarify the location of the under-counter dishwasher; it is shown in two different locations on sheets P1.1 and P1.2. Where are the water supply and drain connections?
3. Clarify the specification for the mat wash; it is described as being the "same as P-6" (exam sink).
4. On sheet P1.2, a single-compartment sink (P-7A) is shown in the same location in room 1128 as a hand sink (K17); are they the same?
5. The ice cuber (K8) is shown as being directly-connected to the water supply system; verify that it has either a listed, integral backflow preventer or an integral air gap conforming to Section 608.13.1, IPC. Reference: Sections 608.1 and 608.3, IPC 2012.
6. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.