Permit Number: T13CM02540
Parcel: 12404003C

Address:
1420 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM02540
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Resize the gas line serving the make-up air unit.
2. Revise the drains for the 3-compartment sink.
3. Verify the size of the grase interceptor per the local amendments to the code.
05/06/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide economizer