Permit Number: T13CM02499
Parcel: 140420100

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM02499
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM02499
2850 E Valencia
Revison

1. Sheet E3.0, service is being increased , cannot use a new 3/0 cu and tie to existing service ground system. Can add
2 ground rods min 6' apart connect 3/0 cu from new service to rods then connect to other items required per 2011 NEC 250.50, indicate on this sheet how new grounding system to be installed. Indicate if existing grounding electrode to be disconnected from existing tie to neutral if new tie to be made.
2. Provide a discription, perferably a spec sheet on new
1200 amp tap box/wireway to be used. How is splicing to be made. Talked to Utility Rep Jennifer Wojner (520-917-8717)
she was understanding that the existing CT enclosure was to be removed and new one installed rather than tap box.Please clearify with her on this installation.
3. E 3.0, indicate what type of Series Rated System to be used on new Panel E.
4. E 3.0, indicate if Panel C is to have fully rated breakers or if a Series Rated System to be used,2011 NEC 110.9,10 and 22.
5. What type of fusing is to be installed at new main disconnects, and is the existing type of fusing at existing mains sufficient for new fault current ?


Ray Majuta
Elect Plan Review
PDSD, Tucson
6/13/2013
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2013 CPIERCE1 REJECT SHELF Completed