Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM02499
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/25/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/26/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM02499 1. The service appears to be upgraded, new 2-sets of 4-500, KCMIL conductors to utility transformer, provide fault current calculations for individual disconnects and panels, insert AIC values in panels. Indicate if AIC at panels above 10K AIC, if full value breakers to be used or Series Rated System. 2. Indicate conductor and conduit sizes from CT enclosure to gutter, also the type of wiring in gutter. Ray T Majuta Elect Plan Review DSD, Tucson 4/26/2013 Ray.Majuta@tucsonaz.gov |
| 04/26/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/26/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/26/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/29/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/29/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/29/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/30/2013 | CPIERCE1 | WWM | REVIEW | Needs Review |