Permit Number: T13CM02495
Parcel: 12517039A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM02495
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/13/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied In the mechanical systems list, all of the rooftop units are shown as having air economizers but in the requirements checklist, RTU-3 and RTU-5 do not have economizers. All of the units apparently are lacking a means of relieving the excess outside air during economizer operation. [Second comment: Complete the mechanical compliance certificate by checking the applicable boxes in the requirements checklist. Checked items shall be supported by specifications (i.e. on the drawings or book specifications) for the activity.] [Initial comment: Show that the proposed HVAC system and equipment meet the requirements of Sections C403.2 and C403.3, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck based upon the 2012 IECC). Reference: Section C303.1, International Energy Conservation Code 2012.
06/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/14/2013 FRODRIG2 FIRE REVIEW Denied
06/14/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please include structural calculations and structural details for the support of a 952 pound exhaust hood. Detail 1/S2.0 is designed for a 500 pound maxium weighted exhaust hood.